LON Digital output 16 ports

Description

  • Triac outputs for 16 thermoelectric or 8 motor-driven actuators with 24 – 230V AC operating voltage
  • On/off, open/close or pulse width modulated operation selectable via software
  • Parameterisable pulse-duration, output limits and motor runtime
  • Automatic valve maintenance function during non-use periods
  • combines sistema MC and two clima AA8

Technical Data

Network TP/FT-10 (FTT10)
Power supply 24V DC, max. 180mA
Load 24-230V AC, max. 500mA per output
Metrics (HxWxD) 85(45) x 175 x 60mm
Mounting DIN rail mounting

Ordering Information

Order No. 121 326